skip to Main Content

Downloads

Catalogue
Product drawings

BalconyDrain

To download the BalconyDrain specification information, click here.

Grate type Channel width
(nominal) mm
Channel depth
(nominal) mm
Specification code PDF DWG RFA
Affiner
85
25
S85-25-A
PDF DWG RFA
103
25
S103-25-A
PDF DWG RFA
103
40
S103-40-A
PDF DWG RFA
5 Star
103
40
S103-40-5S
PDF DWG RFA
Linéaire
85
25
S85-25-L
PDF DWG RFA
103
25
S103-25-L
PDF DWG RFA
103
40
S103-40-L
PDF DWG RFA
Tile
85
25
S85-25-T
PDF DWG RFA
103
25
S103-25-T
PDF DWG RFA
103
40
S103-40-T
PDF DWG RFA

RainTrak®

To download the RainTrak®  specification information, click here.

Type Grate type Channel width
(nominal) mm
Specification code PDF DWG RFA
RainTrak-O
Linéaire
75
RTO75L
PDF DWG RFA
100
RTO100L
PDF DWG RFA
123
RTO123L
PDF DWG RFA
Affiner
75
RTO75A
PDF DWG RFA
100
RTO100A
PDF DWG RFA
123
RTO123A
PDF DWG RFA
RainTrak-E
Linéaire
75
RTE75L
PDF DWG RFA
100
RTE100L
PDF DWG RFA
123
RTE123L
PDF DWG RFA
Affiner
75
RTE75A
PDF DWG RFA
100
RTE100A
PDF DWG RFA
123
RTE123A
PDF DWG RFA

ProfiLine

To download the ProfiLine specification information, click here.

Grates
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No.
Stainless Steel
Part No.
5 Star Heelsafe® Anti-Slip 500 123 20 1.6 - - 141709 DWG
5 Star Heelsafe® Anti-Slip 1000 123 20 3.2 - - 141710 DWG
Slotted 500 123 20 1.0 00277 DWG PDF 00273 DWG PDF
Slotted 1000 123 20 2.2 00276 DWG PDF 00272 DWG PDF
Access units and grates
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No. & DWG
Stainless Steel
Part No.
5 Star Heelsafe® Anti-Slip grate 390 390 20 3.1 - - 141851 DWG PDF
Mesh grate 390 390 20 3.8 38570 DWG PDF - -
Access frame 400 400 75-105 3.1 38801 DWG PDF 38803 DWG PDF
Access frame extension 395 395 50 1.3 38685 DWG PDF 38686 DWG PDF
Access frame extension 395 395 75 1.9 38687 DWG PDF 38688 DWG PDF
Channels
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No.
Stainless Steel
Part No.
Shallow section 500 130 55-77 3.1 36940 DWG PDF 36942 DWG PDF
Shallow section 1000 130 55-77 4.9 36941 DWG PDF 36943 DWG PDF
Intermediate section 500 130 75-105 3.3 36789 DWG PDF 36837 DWG PDF
Intermediate section 1000 130 75-105 5.4 36788 DWG PDF 36836 DWG PDF
Deep section 500 130 105-165 3.8 36807 DWG PDF 36855 DWG PDF
Deep section 1000 130 105-165 6.4 36806 DWG PDF 36854 DWG PDF
Adjustable length channels
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No.
Stainless Steel
Part No.
Shallow section 50-600 140 55-77 2.1 36948 DWG PDF 36949 DWG PDF
Intermediate section 50-600 140 75-105 2.2 36790 DWG PDF 36838 DWG PDF
Deep section 50-600 140 105-165 2.9 36808 DWG PDF 36856 DWG PDF
Adjustable corner
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No.
Stainless Steel
Part No.
Adjustable corner 300 300 - 1.5 38634 DWG PDF 38643 DWG PDF
End plates
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No.
Stainless Steel
Part No.
Shallow section n/a 130 55-77 0.1 36950 36951
Intermediate section n/a 130 75-105 0.1 36793 36841
Deep section n/a 130 105-165 0.2 36811 36859
Drainage duct
Description Length
(mm)
Width
(mm)
Height
(mm)
Weight
(kg)
Galvanised
Part No.
Stainless Steel
Part No.
Drainage duct 2000 100 30 2.4 00328 DWG PDF 00307 DWG PDF
Installation files

BalconyDrain
Description PDF DWG
BalconyDrain with double waterproof membrane and tile flooring PDF DWG
BalconyDrain with single waterproof membrane and tile flooring PDF DWG

RainTrak®
Description PDF DWG
RainTrak-O PDF DWG
RainTrak-E PDF DWG
ProfiLine
Specification clause

BalconyDrain
Grate type Channel width
(nominal) mm
Channel depth
(nominal) mm
Specification code Specification clause
Affiner
85
25
S85-25-A
The floor channel and grates are to be type S-85-25-A (85mm wide, 25mm deep channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
103
25
S103-25-A
The floor channel and grates are to be type S-103-25-A (103mm wide, 25mm deep channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
103
40
S103-40-A
The floor channel and grates are to be type S-103-40-A (103mm wide, 40mm deep channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
5 Star
103
40
S103-40-5S
The floor channel and grates are to be type S-103-40-5S (103mm wide, 40mm deep channel with 5 Star grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
Linéaire
85
25
S85-25-L
The floor channel and grates are to be type S-85-25-L (85mm wide, 25mm deep channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
103
25
S103-25-L
The floor channel and grates are to be type S-103-25-L (103mm wide, 25mm deep channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
103
40
S103-40-L
The floor channel and grates are to be type S-103-40-L (103mm wide, 40mm deep channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
Tile
85
25
S85-25-T
The floor channel and grates are to be type S-85-25-T (85mm wide, 25mm deep channel with Tile grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
103
25
S103-25-T
The floor channel and grates are to be type S-103-25-T (103mm wide, 25mm deep channel with Tile grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.
103
40
S103-40-T
The floor channel and grates are to be type S-103-40-T (103mm wide, 40mm deep channel with Tile grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channels overall length, outlet position and outlet diameters are specified on drawing number/s ______.All components used within the scope of the systems are shown on drawing number/s ______. All work should be carried out strictly in accordance with the manufacturer's instructions and the installation details set out on drawing number/s ____.

RainTrak®
Type Grate type Channel width
(nominal) mm
Specification code Specification clause
RainTrak-O
Linéaire
75
RTO75L
The floor channel and grates are to be type RTO75L (75mm wide, variable depth channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd.The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
100
RTO100L
The floor channel and grates are to be type RTO100L (100mm wide, variable depth channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd.The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
123
RTO123L
The floor channel and grates are to be type RTO123L (123mm wide, variable depth channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd.The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
Affiner
75
RTO75A
The floor channel and grates are to be type RTO75A (75mm wide, variable depth channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd.The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
100
RTO100A
The floor channel and grates are to be type RTO100A (100mm wide, variable depth channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd.The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
123
RTO123A
The floor channel and grates are to be type RTO123A (123mm wide, variable depth channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd.The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
RainTrak-E
Linéaire
75
RTE75L
The floor channel and grates are to be type RTE75L (75mm wide, variable depth channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channel will be supplied with an enclosed sill section, made to suit as per dimensions on drawing number __________. The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
100
RTE100L
The floor channel and grates are to be type RTE100L (100mm wide, variable depth channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channel will be supplied with an enclosed sill section, made to suit as per dimensions on drawing number __________. The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
123
RTE123L
The floor channel and grates are to be type RTE123L (123mm wide, variable depth channel with Linéaire grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channel will be supplied with an enclosed sill section, made to suit as per dimensions on drawing number __________. The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
Affiner
75
RTE75A
The floor channel and grates are to be type RTE75A (75mm wide, variable depth channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channel will be supplied with an enclosed sill section, made to suit as per dimensions on drawing number __________. The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
100
RTE100A
The floor channel and grates are to be type RTE100A (100mm wide, variable depth channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channel will be supplied with an enclosed sill section, made to suit as per dimensions on drawing number __________. The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
123
RTE123A
The floor channel and grates are to be type RTE123A (123mm wide, variable depth channel with Affiner grates) grade 304/316 stainless steel, as supplied by ACO Pty Ltd. The channel will be supplied with an enclosed sill section, made to suit as per dimensions on drawing number __________. The channels overall depth, length, outlet position/s and outlet diameter/s are specified on drawing number/s __________.All components used within the scope of the systems are shown on drawing number/s __________. All work should be carried out strictly in accordance with the manufacturers instructions and the installation details set out on drawing number/s __________.
ProfiLine

The channel drainage shall be ACO ProfiLine – as supplied and manufactured by ACO Pty Ltd. The ProfiLine channel features perforations to facilitate subsurface drainage and a Stainless 5 Star Heelsafe Anti-Slip / Stainless Slotted / Stainless Mesh / Galvanised Slotted / Galvanised Mesh grate for surface drainage.

SUBSCRIBE
Close
SUBSCRIBE